FAO ............................ Paddy..............

Go down  Message [Page 1 of 1]

Mario

avatar
moderator
Here ya go matey.............






it looks like this was the old unit from inside the house before re-wire............plus i followed the main line back into the house and it plugs into a normal 13 amp socket(?)



cheers mate,appreciate your help Very Happy


_________________
just luvvin dubbin,just smile it might make someones day

Mario

avatar
moderator
i forgot to add................

all my double sockets and lights all run from this unit in my garage n workshop..


_________________
just luvvin dubbin,just smile it might make someones day

paddy

avatar
All was looking good until this bit:


Mario wrote:..........plus i followed the main line back into the house and it plugs into a normal 13 amp socket(?)

The consumer unit in the garage needs to be fed from a dedicated supply in the consumer unit in the house with a 30A breaker / fuse protecting it all. No point having a 30A fuse in the garage with a 13A socket upstream of it.

Really you need to scrap the cable feeding the garage consumer unit, and re-wire that first into a dedicated breaker / fuse in the consumer unit in the house. THEN use one of the spare 30A fuses in te garage consumer unit to be the feed for the compressor.

Make sense ?

substandard

avatar
Mario wrote:plus i followed the main line back into the house and it plugs into a normal 13 amp socket(?)

lol Quality!!

Mario

avatar
moderator
paddy wrote:All was looking good until this bit:


Mario wrote:..........plus i followed the main line back into the house and it plugs into a normal 13 amp socket(?)

The consumer unit in the garage needs to be fed from a dedicated supply in the consumer unit in the house with a 30A breaker / fuse protecting it all. No point having a 30A fuse in the garage with a 13A socket upstream of it.

Really you need to scrap the cable feeding the garage consumer unit, and re-wire that first into a dedicated breaker / fuse in the consumer unit in the house. THEN use one of the spare 30A fuses in te garage consumer unit to be the feed for the compressor.

Make sense ?



Yes matey it does and once again thanks for this ^^^.................i really hate electrics lol


_________________
just luvvin dubbin,just smile it might make someones day

paddy

avatar
No worries, Mario. I'll have a look through my old sales samples & see if I've got anything that you will need too.

Mario

avatar
moderator
paddy wrote:No worries, Mario. I'll have a look through my old sales samples & see if I've got anything that you will need too.

thanks matey Very Happy


_________________
just luvvin dubbin,just smile it might make someones day